Isolationssystemer for datacenter luftkorridorer. Del 2. Kolde og varme korridorer. Hvilken isolerer vi?

Der er to muligheder for installation af et containeriseringssystem i et allerede operationelt maskinrum (om installation af isoleringssystemer i nye maskinrum vil jeg fortælle i næste del). I det første tilfælde isolerer vi den kolde korridor, og i det andet den varme korridor. Hver mulighed har sine egne kendetegn, fordele og ulemper.

Isolering af den kolde korridor

Funktionsprincip: for at lede den kolde luftstrøm ind i korridoren anvendes perforerede plader placeret foran skabets dør. Den varme luft "kastes" ud i det samlede rum.

Isolationssystemer for datacenter luftkorridorer. Del 2. Kolde og varme korridorer. Hvilken isolerer vi?

Montering af kabinetter: for at isolere den kolde korridor placeres skabskonditioneringerne langs rummets omkreds og puster den kolde luftstrøm under det falske gulv. Her står monteringsskabene i en række ansigt til ansigt.

Fordele:

  • relativt lav omkostning,
  • nem skalering: skabskonditioneringen kan installeres på ethvert ledigt sted langs maskinrummets omkreds.

Ulemper:

  • vanskelig skalering: i flere korridorer kan der opstå problemer med luftens ensartethed i de forskellige rækker,
  • i tilfælde med højt belastede enheder er det svært at øge den lokale tilførsel af kold luft, da det kræver installation af yderligere perforerede plader i det falske gulv,
  • ikke de mest komfortable arbejdsforhold for personalet, da hele rummet er i den varme zone.

Konstruktive kendetegn:

  • der er behov for en ekstra højdereserve for installation af det falske gulv og ekstra plads til at installere rampe ved indgangen,
  • da containeren isoleres langs den indre omkreds af korridoren, er der behov for isolering af fronten i kabinettet samt en afskærmning under kabinettet foran.

Hvem det passer til: små serverrum eller maskinrum med lav belastning (op til 5 kW per kabinet).

Den varme korridor

Funktionsprincip: i tilfælde af isolering af den varme korridor anvendes inter-rack klimaanlæg, der puster kold luft ind i det samlede rum.

Isolationssystemer for datacenter luftkorridorer. Del 2. Kolde og varme korridorer. Hvilken isolerer vi?

Installation of racks: cabinets are installed in rows, backs facing each other. In this arrangement, air conditioners are placed in line with the cabinets to minimize the length of the airflow and thereby enhance the cooling system's efficiency. Hot air is expelled into a closed container and then returned to the air conditioner.

Fordele:

  • a reliable, high-performance solution that can be used with heavily loaded racks, as well as in rooms with low ceilings, since it does not require either a raised floor or an upper plenum for installation,
  • easy scalability due to each corridor being independent,
  • ensures a comfortable environment for personnel in the room.

Ulemper:

  • price: in this option, more air conditioners are needed, with each container requiring its own backup air conditioner,
  • interior air conditioners take up space that could be used for server cabinets,
  • scalability challenges: adding air conditioners is only possible if additional connection points are planned in advance.

Konstruktive kendetegn:

  • the room does not require additional height clearance,
  • the container is insulated along the external perimeter of the corridor,
  • cabinets require insulation on the front edge and a base plate, as well as insulation for all cabinet tops,
  • for end cabinets in the corridor, insulation on the sides of the cabinet and base is needed around the external perimeter.

Isolationssystemer for datacenter luftkorridorer. Del 2. Kolde og varme korridorer. Hvilken isolerer vi?

Who is it suitable for: small and medium server rooms with high loads (up to 10 kW per rack).

A special case: containerized systems with a closed cooling loop for cabinets.

Principle of operation: air conditioners are installed next to or inside the cabinets, creating unified closed hot and cold zones. Air exchange occurs within the cabinet (or a small group of cabinets).

Fordele:

  • a high-performance solution that is used with loaded racks or in rooms not intended for IT equipment placement (the container also serves as a protective shell for IT equipment),
  • can be used in rooms with low ceilings.

Ulemper:

  • the high cost of the solution excludes the possibility of mass placement of cabinets,
  • begrænset skaleringsmulighed: for at sikre redundans kræver hvert sæt en separat airconditioner,
  • komplicering af brandslukningssystemet: hvert lukket skab bliver til en separat sektion, der kræver sit eget sæt overvågningssensorer og et lokalt brandslukningssystem.

Konstruktive kendetegn:

  • the room does not require additional height clearance,
  • skabets konstruktion omfatter en helt lukket kreds, herunder muligheden for beskyttelse efter IP.

Hvem det passer til: dem der har brug for at placere højtydende computerkomplekser (op til 20 kW pr. rack).